Standard:• ISO 1716Main Features:1. The apparatus including: calorimeter apparatus, high-p
WhatsApp : +86 13816217984
Email : info@qinsun-lab.com
• ISO 1716
1. The apparatus including: calorimeter apparatus, high-pressure oxygen bomb, cold water installations, computer and control system (which can record and display the curve), LCD screen and software; Crucible made of stainless steel;
2. Box paint treatment; all internal parts are made of stainless steel, corrosion-resistant, easy to clean;
3. Ignition wire break is detection,and automatic ignition;
4. The test procedure automatically turn off;
5. Test abnormalities has sound alarm;
6. Computer control system;
7. Control box with USB / RS232 serial port with an external brand desktop or laptop operating control; High degree of automation, test procedure safe and reliable, easy to operate;
1. Bomb capacity: (300 ± 50) mL;
2. Oxygen bomb pressure range: 0.5 ~ 3.5MPa, no leakage. The bomb pressure 21Mpa;
3. Timer: accuracy of 0.5s;
4. Maximum power: 0.5KW;
5. Ambient temperature: (10 ~ 35) ºC, humidity ≤80%;
6.Heat capacity of the instrument: about 10000J / K;
7. Heat repeatability error: ≤0.2%;
8. Temperature range: (4.5-50) ºC;
9. Temperature detection: 0.0001 ºC resolution, using the PT100 sensor;
10. Inner cylinder volume: 2000ml; Oxygen bomb Sealing: oxygenation pressure 2.5 ~ 3.5MPa, no leakage;
11. Motor power: 3W; stirring speed: the inner tube (375r / min);
12. Power supply voltage: AC220V ± 10% 50Hz.
Disclaimer: The above content is for reference and communication only among industry insiders, and does not guarantee its accuracy or completeness. According to relevant laws and regulations and the regulations of this website, units or individuals who purchase related items should obtain valid qualifications and qualification conditions.